Magnetics Calculators29 instruments

Transformer Turns Design

Primary & secondary turns from voltage, frequency, Bₘₐₓ and core area.

N=V4.44fABN=\frac{V}{4.44fAB}
Fig. 1 Transformer schematic: winding bumps scale with turns
230 V12 VNₚ = 1080Nₛ = 57laminated core · Aₑ = 8 cm²
Fig. 2 Primary & secondary voltage and core flux over two cycles
010203040-2000200time (ms)V
v_pv_sΦ (scaled)
hover / touch plot to probe
Inputs drag, tap ± or type (SI suffixes ok: 4k7 → 4.7k)
Drive waveform
V
V
Hz
T
cm²
Results
Primary turns NpN_p
1080exact 1,079
Secondary turns NsN_s
57
Turns ratio aa
18.95 : 1
Volts per turn
213 mV
Actual BmaxB_{max}
1.2 T
Impedance ratio
359 : 1

§ How it works

Faraday's law ties the winding voltage to the rate of change of core flux, v=N Ae dBdtv = N\,A_e\,\frac{dB}{dt}. For a sinusoid with peak flux density BmaxB_{max} this gives the classic transformer EMF equation:

Vrms=4.44 f N Ae Bmax⇒Np=Vp4.44 f Ae BmaxV_{rms} = 4.44\,f\,N\,A_e\,B_{max} \quad\Rightarrow\quad N_p = \frac{V_p}{4.44\,f\,A_e\,B_{max}}

(4.44=2π/24.44 = 2\pi/\sqrt2.) For a bipolar square wave the flux ramps linearly and the constant becomes 4. Choosing BmaxB_{max} below saturation, and low enough to keep core loss acceptable, fixes the minimum primary turns. The secondary follows from the ideal ratio:

VpVs=NpNs=a,IpIs=1a,Zp=a2Zs\frac{V_p}{V_s} = \frac{N_p}{N_s} = a, \qquad \frac{I_p}{I_s} = \frac1a,\qquad Z_p = a^2 Z_s

Turns are rounded up (more turns → lower flux). In practice add 5–10 % to NsN_s to compensate for winding resistance drop under load. Flux lags the voltage by 90°, as the plot shows.