American Wire Gauge is a geometric series: AWG 36 is defined as 0.005 in and AWG 0000 as 0.46 in, with 39 steps between them:
Every 6 gauges halve the diameter; every 3 gauges halve the area (and double the resistance). Resistance follows from the resistivity with a linear temperature coefficient:
In magnetics the current density is the usual design limit for windings: 2–4 A/mm² for passively cooled transformers, up to 6–8 A/mm² for short-duty or forced-air designs. Enamel insulation adds roughly 5–10 % to the diameter, so real turns-per-cm will be slightly lower than shown. At high frequency, check the skin-depth calculator; strands thicker than ~2δ waste copper.